GE3
                                          cast iron high efficiency sectional boiler,
                                          for gas/oil fuels
                                          chaudiere en fonte haut rendement,
                                          pour le chauffage central
                               =
cod. 3540Z970 - Rev. 01 - 02/2018

                                          INSTALLATION, SERVICE AND USER INSTRUCTIONS
                                          INSTRUCTIONS D'UTILISATION, D'INSTALLATION ET D'ENTRETIEN
GE3

        (1        THE  MARKING CERTIFIES THAT THE PRODUCTS MEET THE ESSENTIAL REQUIREMENTS OF
                  THE RELEVANT DIRECTIVES IN FORCE.

                  THE DECLARATION OF CONFORMITY MAY BE REQUESTED FROM THE MANUFACTURER.

    1. Technical informations ............................................................................................................ 3
    2. Dimensions and technical data............................................................................................... 3
    3. Packing and shipment ............................................................................................................ 5
    4. Installation .............................................................................................................................. 6
    5. Testing .................................................................................................................................... 7
    6. Service.................................................................................................................................... 8

2                                                               cod. 3540Z970 - Rev. 01 - 02/2018
GE3
1. Technical informations

1.01 Introduction
*( boiler is a new heating generator with high ef¿ciency,
for central heating system suitable for burners using oil

                                                                                                                           English
or gas.
The boiler body is built by cast iron sections joined togheter
by mean of biconical nipples and tie rods. Sections ¿ns
are especially developed to achieve the best ef¿ciency
of the boiler in order to save on fuel consumption. The
boiler body insulation is provided by mineral high density
¿bers that minimizes the body heat lost.

Key
                                                                                    1
1 Control thermostat                                                                    2
2 Security thermostat manual resetting                                                      3
3 Thermometer                                                                                   Fig. 1

1.02 Control and securities devices operation

                                                                                                                           Français
Regulating thermostat, manual resetting 3 (¿g. 1)
It operates when the boiler temperature, during the heating mode reach such a level that can use a danger situation.
Before resetting this thermostat ask for Quali¿ed Serviceman to inspect the appliance.
Control thermostat 1 (¿g. 1)
It allows to control the boiler temperature by mean of its knobs.
This thermostat controls the burner.

2. Dimensions and technical data
2.01 Flue gas path

                                                cod. 3540Z970 - Rev. 01 - 02/2018
                                                                                                                       3
GE3
               2.02 Dimensions and technical data (¿g. 2 - tab. 1)
English
Français

                                                                              Fig. 2
               Key
               a1 Flow 1 1/4"
               a2 Return 1 1/4"
               a3 Boiler drain 1/2"
               a4 Flue connection 120-130 mm
               a5 Burner hole 105 mm

               Tab. 1

                            Heat and D.H.W.     Heat and                                                            Combustion
                                                                              N°             Water capacity
                  Model      (net) gas+oil    D.H.W. output                                                        chamber lenght
                                                                           element                dm3
                                 Max.             Max.                                                                 mm
                GE 3 - 25        27,8                25,0                       3                   13                      350
                GE 3 - 35        38,8                35,0                       4                   17                      450
                GE 3 - 45        49,9                45,0                       5                   21                      550
                GE 3 - 55        59,6                54,                       6                   25                      650

                                                                  Combustion Combustion                  Water load losses
                            Working                                                                                               Weight
                                                                   chamber    chamber
                 Model      pressure     A      B           C                                                                     of unit
                                                                   load loss   volume
                               bar                                                                       ¨t 10      ¨t 20           kg
                                                                    ¨p mbar     dm3
                GE 3 - 25       6       400    750      380             0,1              20,15            1,8         -            115
                GE 3 - 35       6       400    750      480             0,15             28,21            4,2         1            145
                GE 3 - 45       6       400    750      580             0,15             36,27            7,2        1,6           175
                GE 3 - 55       6       400    750      680             0,2              52,39             11        2,3           205

               N.B.: - Max. water temperature for the heating system is 90° C. - Min. water temperature for the heating
               system is 45° C.

           4                                                    cod. 3540Z970 - Rev. 01 - 02/2018
GE3
2.03 Pressure drop (¿g. 3)
Pressure drops according to the boiler size are speci¿ed on the following diagram and refer to temperature diffe-
rence between Àow and return comprises between 10 and 20°C.
                                           1000
                                            900

                                                                                                                        English
                                            800
                                            700
                                           600
                                           500

                                           400

                                           300

                                           200
                               Δp (mbar)

                                           100
                                            90
                                            80
                                            70
                                            60

                                            50

                                                                                                                        Français
                                            40

                                            30

                                            20

                                            10
                                                  1        2      3    4    5    6   7 8 9 10   20
                                                                      Q (m3/h)

                                                                   Fig. 3
3. Packing and shipment
Boiler is delivered complete assembled in a wood crate.

                                                                   Fig. 4

                                                      cod. 3540Z970 - Rev. 01 - 02/2018
                                                                                                                    5
GE3
               Electrical diagram
                                                                                                        220V
                                                                                                      ~ 50Hz
English

                                                                                                  L

                                                                                                 TR

                                                                                                 TS
Français

                                                                                                         B
               Key
               TR boiler thermostat
               TS Safety thermostat
               B Burner                                                                     N

                                                                                                         Fig. 5

               4. Installation
               It is law that all gas appliances are installed by Competent Persons, in accordance with the regulations. Failure to
               install appliances correctly lead to prosecution, it is your own interest, and that of safety, to ensure that the law is
               coplied with. Manufacturers instructions must NOT be taken in any way as over-riding statutory obligations, special
               care must be paid to conform with law and regulation concerning building and location of the chimney.

               4.01 Hydraulic connections
               Boiler must be connected to the system according to boiler back part indications and those provided at ¿g. 2. Pipe
               must be free of any kind of strain and security valves must be provided in both central heating system and domestic
               hot water system location of such security valves be as close is possible to the boiler and between the boiler and
               valve no obstructions or gate valves must be placed.
               The boiler is not supplied with expansion tank it has to be provided during the boiler installation. It is advised that
               the pressure in the hydraulic system has to be between 0,5 and 1 bar measured in cold water condition.

               4.02 Connection to the chimney
               It is recommended to connect the boiler to a good working chimney built according to the regulations. The con-
               nection between boiler and chimney must be done by using suitable ma terial proof against high temperature and
               corrosion. Where Àue sections have to be connected it is advised pay attention to avoid leaking and provided good
               insulation through all the Àue length to avoid condensing problem.

           6                                                 cod. 3540Z970 - Rev. 01 - 02/2018
GE3
5. Testing
5.01 Before the ¿rst light of the boiler
Before the ¿rst light of the boiler follow these check list:
a) check the system is ¿lled with water at the right pressure;

                                                                                                                               English
b) check against any leakage of water fuel;
c) check that the correct electric power is supplied to the unit;
d) check size and perfect Àue installation;
e) check against any type of Àammable materials where the boiler is installed;
f) check the burner has the right heat input according to the boiler size;
g) control that the water valves are open.

5.02 First lighting
After the boiler preliminaries checking , the appliance can be lights in the following way;
1) Open the fuel gate valve.
2) Set the regulating thermostat at the required temperature level.
After above operations the burner will start to run and the boiler will begin to work.

                                                                                                                               Français
5.03 After the ¿rst lighting
After the ¿rst lighting it is advisable check:
burner works properly, this checking must be done by appropriate instruments.
Thermostats operate correctly.
Water Àows through the system.
Smoke gases evacuate through the Àue duct.

5.04 Switch off
To turn off the unit for a short period it is enough to switch off the switch 4 (¿g. 1) on the control panel.
If the boiler has to be stopped for long period beside to act by the switch 4, it is necessary to cut the supply of fuel
by mean of the gate valve, in winter season, to avoid damages due to the frost it is necessary to add the antifrost
liquid in the system or to drain it completely.

                                              cod. 3540Z970 - Rev. 01 - 02/2018
                                                                                                                           7
GE3
               6. Service
               The after sale service must be carried out only Quali¿ed Plumbers. It is advise to service the boiler at least once
               a year, before the winter season. Check must include the boiler cleaning, the perfect operation of the controls and
               the burner.
English

               Furthermore the Àue duct conditions have to be inspected.

               6.01 Boiler cleaning
               Cut out electric power.
               The front panels 1, 2, 3 (¿g. 6).
               Clean the boiler internal parts.
               Check the Àue duct and if necessary clean it.
               The burner service must be done according the Manufacture Instructions.
Français

                                                                                               3          2

                                                                          Fig. 6

           8                                               cod. 3540Z970 - Rev. 01 - 02/2018
GE3

    FR        LE MARQUAGE > ATTESTE QUE LES PRODUITS SONT CONFORMES AUX EXIGENCES
              ESSENTIELLES DE L'ENSEMBLE DES DIRECTIVES QUI LEURS SONT APPLICABLES.

              LA DÉCLARATION CE DE CONFORMITÉ PEUT ÊTRE DEMANDÉE AU FABRICANT.

1. Présentation ......................................................................................................................... 10
2. Caractéristiques dimensionelles et techniques .................................................................... 10
3. Conditionnement .................................................................................................................. 12
4. Installation ............................................................................................................................ 13
5. Contrôles .............................................................................................................................. 14
6. Entretien ............................................................................................................................... 15

                                                           cod. 3540Z970 - Rev. 01 - 02/2018
                                                                                                                                                  9
GE3
            1. Présentation
            1.01 Introduction
            La chaudière GE3 est un nouveau générateur de chaleur
            à haut rendement, pour le chauffage. Le corps de chauffe
English

            est constitué d'éléments en fonte nipples dont le pro¿l à été
            particulèrement étudié et qui permet des hautes performances
            thermiques et par consequence economie d'energie.
            L'isolation de la chaudière est constitué d'un epais matelas
            de laine de verre que reduit au minimum la dispersion de la
            chaleur vers l'exterieur.

            Legende
            1 Aquastat de réglage chaudière                                                  1
                                                                                                 2
            2 Aquastat de sécurité à réarmement manuel                                               3
            3 Thermomètre
                                                                       Fig. 1
            1.02 Fonctions des dispositifs de réglage et sécurité
Français

            Aquastat de sécurité à réarmement manuel
            Il intervient lors que la température chaudière, atteint des valeurs superièurs aux températures reglées sur les
            aquastats de fonctionnament.
            Lors que cet aquastat intervient il y a lieu de contacter votre service après vente.
            Aquastat de réglage chaudière
            Il permet le réglage de la température de la chaudière, cet aquastat commande seulement le brûleur dans la
            phase chauffage.

            2. Caractéristiques dimensionelles et techniques
            2.01 Parcours fumées

           10                                            cod. 3540Z970 - Rev. 01 - 02/2018
GE3
2.02 Données dimensionelles et techniques (¿g. 2 - tab. 1)

                                                                                                                                                   English
                                                                                                                                                   Français
                                                                          ¿g. 2
Legende
 a1    Départ installation - 1 1/4"
 a2    rétour installation - 1 1/4"
 a3    Vidange chaudière - 1/2"
 a4    Raccordement cheminée - 120-130 mm
 a5    Ori¿ce brûleur - 105 mm

Tab. 1
                Débit
                                                                          Longueur
             calorifique   Puissance                        Contenu
                                                N°                       chambre de
  Modèle        (PCI)      nominale                          en eau
                                             éléments                    combustion
              gaz+fioul      Max.                             dm3
                                                                            mm
                Max.

 GE 3 - 25     27,8            25,0             3             13            350
 GE 3 - 35     38,8            35,0             4             17            450
 GE 3 - 45     49,9            45,0             5             21            550
 GE 3 - 55     59,6                         6             25            650

                                                                                Perte             Volume
               Pression max.                                                                                        Perta de          Poid
                                                                              de charge          chambre
  Modele        de exercice            A                B           C                                               charge            corps
                                                                              chambre           combustion
                    bar                                                                                                                kg.
                                                                             combustion            dm3
                                                                              Dp mbar                        Dt 10             Dt20
 GE 3 - 25            6                400          750            380             0,1            20,15       1,8               -     115
 GE 3 - 35            6                400          750            480            0,15            28,21       4,2               1     145
 GE 3 - 45            6                400          750            580            0,15            36,27       7,2              1,6    175
 GE 3 - 55            6                400          750            680            0,2             52,39       11               2,3    205

N.B.: - La température maxi d'exercice chauffage est de 90° C. - La température mini chauffage est
de 45° C.

                                                            cod. 3540Z970 - Rev. 01 - 02/2018
                                                                                                                                              11
GE3
            2.03 Données des pertes de charge (¿g. 3)
            Les pertes de charge du circuit hydraulique par modèle de chaudière, speci¿ées dans le diagramme ci dessous,
            sont les pertes de charge du débit d'eau dans la chaudière à la puissance nominale.
                                                      1000
                                                       900
English

                                                       800
                                                       700
                                                      600
                                                      500

                                                      400

                                                      300

                                                      200
                                          Δp (mbar)

                                                      100
                                                       90
                                                       80
                                                       70
                                                       60
Français

                                                       50

                                                       40

                                                       30

                                                       20

                                                       10
                                                             1         2       3    4    5    6   7 8 9 10   20
                                                                                   Q (m3/h)

                                                                               Fig. 3

            3. Conditionnement
            La chaudière est livrée assemblée sous caisse bois.

                                                                               Fig. 4

           12                                                    cod. 3540Z970 - Rev. 01 - 02/2018
GE3
Schéma éléctrique

                                                               220V
                                                             ~ 50Hz

                                                                                                                        English
                                                          L

                                                     TR

                                                     TS

                                                                                                                        Français
Légende
TR Aquastat de réglage
TS Aquastat de sécurité
B Brûleur

                                                                   B
                                                                                                 Fig. 5

                                               N

4. Installation
L'installation de la chaudière doit être effectuée par du Personnel Quali¿é, suivant les instructions du fabricant et
les prescriptions en vigueur.

4.01 Raccordement hydraulique
Effectuer le raccordement hydraulique selon les indications de la ¿g. 2. Le racordement doit être executé d'une
façon que les tubes soient libres de tensions.
Il est obligatoire monter les soupapes de sécurité dans le circuit, hydraulique (3 bar).
La chaudière n'est pas fournie avec vase d'expansion; son montage doit être effectué par l'installateur.
On rappelle que la pression dans l'installation à froid doit être entre 0,5 et 1 bar.

4.02 Raccordement de la cheminée
Il est recommandé de respecter les normes en vigueur.
Le conduit entre chaudière et cheminée doit resister aux hautes temperatures et à la corrosion et doit être com-
pletement étanché. Le conduit de fumée sera éventuellement tubé en cas de condensation.

                                             cod. 3540Z970 - Rev. 01 - 02/2018
                                                                                                                   13
GE3
            5. Contrôles
            5.01 Avant le premier allumage
            Avant le 1er allumage il est conseillé de contrôler que:
            a) le circuit soit chargé à la bonne pression et purgé;
English

            b) il n'y ait pas des fuites d'eau ou de combustible;
            c) l'alimentation éléctrique soit correcte;
            d) le raccordement à la cheminée soit étanché;
            e) il n'y ait pas du materiel inÀammable pres de l'appareil;
            f) le brûleur soit proportionné à la puissance de la chaudière;
            g) le robinets de barrage soient ouverts;

            5.02 Premièr allumage
            Effectué les contrôles avant l'allumage, proceder au 1er allumage selon la sequence suivante:
            Ouvrir le robinet de barrage combustible.
            Régler l'aquastat de reglage à la temperature choisie.
Français

            Donner courant à l'interrupteur en amont de la chaudière.
            A ce point le brûleur s'allume et l'appareil fonctionne.

            5.03 Contrôles après l'allumage
            Après le 1er allumage il convient de contrôler que:
            Le brûleur fonctionne correctement (à effectuer avec des appareillage speci¿ques).
            Le fonctionnement des aquastats soit correct.
            L'eau circule dans l'installation.
            L'evacuation des fumées s'effectue correctement.

            5.04 Arrêts
            Pour des longues periodes d'arret, en plus de fermer l'interrupteur dans le tableau de bord, il faut fermer le robinet
            de barrage du combustible. Pour des longues periodes d'arret pendant l'hiver il est necessaire, pour eviter les
            dommages causes par le gel, d'introduir dans l'installation de l'antigel.

           14                                            cod. 3540Z970 - Rev. 01 - 02/2018
GE3
6. Entretien
L'entretien de chaudière doit être effectué par du Personnel Quali¿é. Il convient d'effectuer le contrôle de l'appareil
au moin une fois par an avant l'hiver. Le contrôle doit regarder, autre le nettoyage de la chaudière et de la cheminée,
le fonctionnement correct de tous dispositifs de contrôle, de securité et du brûleur.

                                                                                                                          English
6.01 Nettoyage de la chaudière
Enlever le courant de la chaudière.
Enlever les panneaux 1,2,3 (¿g. 6).
Proceder au nettoyage de la chaudière
Contrôler que le conduit des fumées soit propre.
Pour le nettoyage du brûleur suivre les instructions du Fabricant.

                                                                                  3            2

                                                                                                                          Français

                                                        Fig. 6

                                              cod. 3540Z970 - Rev. 01 - 02/2018
                                                                                                                     15
)(552/,6S$
         Via5LWRQGDD
6DQ%RQLIDFLR9HURQD,7$/<
          ZZZIHUUROLFRP
  0DGHLQ,WDO\)DEULTXpHQ,WDOLH
Vous pouvez aussi lire